Chapter 5: Using the Web Interface
62
3. To select a date, do either of the following:
Click Today if you want to select today.
Note: On the calendar, the date for today is marked with a red frame.
Click any date on the calendar.
Setting Data Logging
The data retrieval feature allows the retrieval of Dominion PX data by an
SNMP manager, such as the data of PDU, line, and circuit breaker.
Dominion PX can store 120 measurements for each sensor in a memory
buffer. This memory buffer is known as the data log. Sensor readings in
the data log can be retrieved using SNMP.
You can configure how often measurements are written into the data log
using the Measurements Per Log Entry field. Since Dominion PX's internal
sensors are measured every second, specifying a value of 60, for example,
would cause measurements to be written to the data log once every
minute. Since there are 120 measurements of storage per sensor,
specifying a value of 60 means the log can store the last two hours of
measurements before the oldest one in log gets overwritten.
Whenever measurements are written to the log, three values for each
sensor are written: the average, minimum and maximum values. For
example, if measurements are written every minute, the average of all
measurements that occurred during the preceding 60 seconds along with
the minimum and maximum measurement values are written to the log.
Note: Dominion PX's SNMP agent must be enabled for this feature to work.
See Enabling SNMP (on page 136) for more details. In addition, using an
NTP time server ensures accurately time-stamped measurements.
Enabling Data Logging
By default, data logging is disabled. Only users having the "Administrator"
or "Change Data Logging Settings" permissions can enable or disable this
feature. See Setting Up Roles (on page 68, on page 69).
To configure the data logging feature:
1. Choose Device Settings > Data Logging. The Data Logging Options
dialog appears.
2. To enable the data logging feature, select the "enable" checkbox in
the Enable Data Logging field.
3. Type a number in the Measurements Per Log Entry field. Valid range
is from 1 to 600. The default is 60.
4. Verify that all sensor logging is enabled. If not, click Enable All in Page
to have all sensors selected.