Chapter 5: Using the Web Interface
73
Mapping the Environmental Sensors
OncethesensorshavebeenphysicallyconnectedtotheDominionPX,
theymustbemappedtotheunitʹslogicalsensorsbeforeDominionPX
willrecognize(anddisplay)thereadingsfromthem.Todothis:s
1. SelectDeviceSettings,andthenselectEnvironmentalSensors.The
EnvironmentalSensorswindowappears.Thepa
gewilllistthe
logicalTemperatureandHumiditysensorsfirst.
2. WhenphysicalsensorsareattachedtotheDominionPX,theywill
appearlistedbelowthelogicalsensors.Temperaturesenorswillbe
listedintheEnvironmentalTemperatureSensorstable,humidity
sensorsintheEnvironmentalHumiditySensorstable.Ifthesensors
arenotattachedproperly,thepagewillstatethatʺNosensorswere
detectedʺ.
3. Forea
chphysicalsensor(shownasarow)inthetable,clickaradio
selectunderthelogicalsensor(shownascolumns)youwanttomap
itto.DominionPXwillnowtrackthissensorsreadingsandwill
displaythemonthehomepagewhenconfigurationisfin
ished.
Ifyoudonotwanttotrackthereadingsofaparticularsensor,leave
thatrowblank.